Water hammer after new boiler installed.
Hi all, I had a new boiler installed last week Worcester Bosch 4000 30KW.
Ever since it was installed on Friday I’ve noticed a water hammer any time the washer is one regularly towards the start and end of every cycle. As well as this I get a clang any time I open a tap either hot or cold both upstairs and downstairs. The quicker I open it the louder the hammer.
I never heard this noise once from my previous boiler. Vaillant 25+ years old.
I had my boiler installed by Boxt, the installer did leave his number and said to drop him a message if any issue within first 4 week so I will probably drop him a text tomorow he was a really miserable guy though so might just do direct to Boxt.
One last point he did install and Shock Arrester as part of the install which I can see and he showed me during instal.
Can this be fixed easily will the installer just say it’s unrelated, or perhaps I need new pipework could really do without any additional work and cost.
But the noise Is driving me mad and I also fear
A leak, especially with the noise when the washer is on. Opening taps slowly does prevent it.
Any help much appreciated.
r/askaplumberUK • u/Pinkies_Daddy • 1d ago
Working in domestic hot water and cold water
reddit.comCan I keep my central heating running from my combo boiler while the domestic hot water is drained and mains water off at the stop cock
r/askaplumberUK • u/Wild-Mix2014 • 1d ago
Unsure of rip-off
Hi all,
From the UK. I have a 1960s build house. We just bought it and the plumbing for drainage to the manhole is clay. We had issues with flushing etc. we had a drainage specialist out to unblock and use a camera to see what's going on.
From the downstairs toilet, it goes into a 90 bend which has sunk about 7mm. Then a meter stretch, then into a 120 bent and then another meter until it's hit the manhole. Some of the segments have small cracks or sunk by 1mm. He is saying to do the job he would have to dig 2 holes. One for the 90 bend to put concrete underneath to lift it. And another so that he can then line both segments of pipe. All this for £1850+VAT. If we excavate ourselves, it's £1550+VAT.
from the upstairs toilet, it comes into a 90 and then 1 meter of pipe. 90 has dropped about 4mm. To line all that (he believes that it should be a problem and would stop any more sinking for the 90) is £200+VAT as would not require any digging.
He has said that if we do that with him, he will drop the £250+VAT for work don't tonight. I can't tell if we are being ripped off or not. Please give second opinions. Need to give a response by mid day tomorrow. Thank you
r/askaplumberUK • u/Either-Loww • 1d ago
Combi mains flow rate
I am considering installing a combo boiler to replace a very old tank and shower pump system in a small 2 bedroom/1 shower room top floor flat. At the moment I am heating ups water tank twice a day and it seems like a waste for the small amount I use.
I have had 2 different plumbers round. Both ran the kitchen tap and said it’s is water flow would be fine for a combo boiler.
However, I have measured flow rate myself and it is only 6.7 L/min which I’ve read is too low for a combo to work properly.
I don’t want to go ahead with this and find the shower pressure is terrible. And I don’t interest why the plumbers are telling me it will be fine.
There is an options for a mains water pump I suppose but I’m concerned that would be very noisy.
What should I do?
r/askaplumberUK • u/Helpful_Signature_92 • 1d ago
Heating upgrade advice: modern gas boiler or air source heat pump?
Hi everyone. I’d appreciate real-world advice from people who’ve made this decision, especially anyone with a Victorian terrace in London.
We’re weighing up replacing our existing boiler with a modern gas system boiler, such as a Viessmann Vitodens, or switching to an air source heat pump (ASHP).
Our home and current system
- 1890s, three-storey Victorian mid-terrace in North East London; family of five.
- Current boiler: 2013 Potterton Titanium 33 kW combi, adapted to heat a 250 L Tempest unvented hot water cylinder.
- Around 40 m² of wet underfloor heating downstairs, with radiators on the upper two floors.
- 8 kWp solar PV array and a 16.1 kWh home battery.
Our gas use was around 10,000 kWh/year before we switched the cylinder to immersion heating. Since then, it appears closer to 7,000–8,000 kWh/year, although that isn’t a weather-adjusted comparison. Hot water is now heated electrically, so our current gas use is mainly for space heating.
Heat pump option
We’ve had a room-by-room heat-loss survey and are considering a proposal for a 10 kW Viessmann 200-A heat pump. The quoted cost is around £7,000 after the £7,500 Boiler Upgrade Scheme grant, with no radiator changes under the Zero Disrupt option. Other installers have discussed different models and possible emitter changes.
One thing we’re trying to understand is the difference between our historical gas use and the heat pump’s projected annual electricity use, including hot water. We’d also like to know how realistic the predicted efficiency and running costs are in practice.
Gas boiler option
Our existing boiler is 13 years old, and we’re considering whether a modern condensing system boiler would be a sensible, lower-cost replacement. I haven’t established how much energy or money a new boiler would save in our particular setup, so I’d be interested in experiences from people who’ve replaced a similar boiler and cylinder system.
Questions
- If you switched from gas to a heat pump in a similar Victorian terrace, what were your actual electricity use, SCOP and running costs compared with the installer’s estimates?
- How have you found the outdoor unit’s noise and appearance in a typical London mid-terrace garden?
- With our relatively modest gas use, existing underfloor heating, solar and battery, would you choose the heat pump or replace the boiler? What figures drove your decision?
Thanks for any experiences or advice!
r/askaplumberUK • u/theperiodproperty • 1d ago
ESI 2-port valve
Have an ESI ES ZV 222L 2-port zone valve that leaked from the spindle through the head unit. Took the cover off the head unit to make sure the electrics/clockwork looked OK and a wire about 5cm/2in with a loop and a bent tail just fell out (see photo).
Any ideas on where it fits back in? A picture of a similar ESI valve with it in place would be worth a 1000 words...
r/askaplumberUK • u/GingerGamer-_- • 1d ago
Pressure
Can anybody help me figure how to repressurise my boiler? I bled the radiator and it completely drained the boiler
r/askaplumberUK • u/shitty_zombies • 1d ago
New Bathroom Advice
gallerySee post above. Any advice or comments are appreciated.
r/askaplumberUK • u/Shoddy-Grand-1073 • 2d ago
Water not turning off to our house
We have an 80’s build house and have been living here for 3 years no problems. Recently, our toilet went wrong and would no longer flush.
We had a plumber out to have a look at it. He told us that there was no way of isolating the toilet itself in order to fix it.
He checked various cupboards around our house, including up in the roof.
He found the tap to turn of the water in our house was completely seized up and said it will snap if he tried to turn it off. He then went out on the road to turn our water off from the mains.
When he did this, the water continues to stay on in our property. Today we have had it switched off at the mains all day, yet we have continued to have fully working water and have done 3 loads of washing despite it supposedly being “off”.
We have a hot water tank and tank in the roof, but can hear that that is still refilling despite being off outside.
We have contacted our water supplier who has come out and has no idea either.
Also to add, our water has always been incredibly cheap (£30 a month, for a large 3 bed property with 3 of us living here). We have never questioned the price as we were first time buyers when we moved in, however, have about 14 showers a week, alongside 4 baths, dishwasher on every day and 3 loads of washing on every other day.
When we spoke to my mum who lives round the corner she said her water bill is double what we are paying and she doesn’t use nearly as much water as us.
We have also noticed that over the past 24 hours our water meter readings haven’t changed at all, despite lots of water being used at our property.
Does anyone have any ideas? Could the water not switching off to our house and incredibly low bills bd connected somehow? Thank you
r/askaplumberUK • u/Shoddy-Grand-1073 • 2d ago
Water not turning off to our house
reddit.comr/askaplumberUK • u/decades_out • 2d ago
This shower won’t run cold
galleryPosting here as well in hopes someone can help me get a non scalding shower.
r/askaplumberUK • u/Alcedema • 2d ago
Danfoss BEM 5000 random clicking bursts
Hey all, is this normal? Bought a house with a BEM 5000 and every now and then it will randomly burst clicks, over a few minutes then go silent for ages. The lights on the front don't seem to change. Never had one of these before so is this normal? Many thanks!
P.S. sorry for the camera angle, I was trying to listen to where the clicking was coming from!
r/askaplumberUK • u/Adventurous-Dish619 • 3d ago
Can't get rid of air in system Worcester Greenstar Si Compact
I'm trying to understand what is happening and advice needed.
Boiler had it's annual service a couple of months ago. Also replaced a radiator to warm up the bathroom a bit better. There was air in the system before but now it seems a lot worse. Rads have been bled again and again and all look fine. There is no loss of water pressure in the boiler but I have topped it up to replace the water removed from bleeding. Water and CH is working fine apart from the gurgling from the pipes.
I run Air Purge for about 10 to 15 minutes and this sorts the problem for about half an hour but then the gurgling starts again.
I have checked all rads and cannot detect any leaking water.
I will be travelling abroad for three months in the next week so the whole system will be switched off. I am hoping this will be fine until I get back when I can get it fixed properly but I would like to know what is going on and what I need to do to fix it.
r/askaplumberUK • u/Economy-Life4235 • 3d ago
A-01 Vokera boiler fault
We are having issues with our boiler, it is a Vokera by Riello boiler and keeps coming up A-01 fault code, we have tried to reset the boiler a good few times and it’s as if it’s firing up then goes red and the same code comes up again, I’ve had a look online and when we turn to run the hot tap and turn it back on it tried to fire up again but just getting the same code again.
We have had a few different engineers out who said everything looks good, electrodes fine, pressure fine and even the condensator, most likely to be the PCB.
Has anyone else had this issue and did this end up being their PCB needing replaced? Been told it’s a bit expensive to have replaced but it’s an absolute must!
I’m currently 6 months pregnant and needing this sorted ASAP!
r/askaplumberUK • u/bluebitc • 3d ago
Valliant TimeSwitch 150 keeps getting stuck on- for example today I got home in the evening and when I checked the timer it had got stuck at 2pm(the end of an "on" period) and the heating had been on that whole time - I turn the dial to the correct time and it works for another few days then gets st
r/askaplumberUK • u/Chriz1416 • 3d ago
Shower Hose with Hex Nut on both ends
I need to replace a shower hose but it has a hex nut on both ends. I'm struggling to find a replacement. I need it to be 1m long. All help is welcome
r/askaplumberUK • u/DependentOk383 • 3d ago
Gas boiler heats radiators but not hot-water cylinder. Electric immersion also stopped working. Any ideas? (Ireland/UK-style system)
Hi everyone,
I’m based in Dublin, Ireland, so just to clarify upfront, this is an Irish/UK-style domestic heating system, not an American setup.
I’ve been having ongoing problems with my hot water and would really appreciate some advice from anyone familiar with these systems. I’m not particularly knowledgeable about plumbing or heating, so apologies if I misuse any terminology.
My setup:
Gas boiler: Glow-worm Energy 18s.
Hot-water cylinder: Large blue insulated storage cylinder with an electric immersion heater.
Motorised valves: Three Myson Power Extra valves, one apparently labelled “HOT”, which I believe controls the hot-water circuit.
Cylinder thermostat: Orange thermostat attached to the side of the cylinder.
Timer: Optimum mechanical 24-hour timer, located underneath the gas boiler.
Room thermostat: IMIT dial thermostat.
As far as I understand, the system should allow us to heat our domestic hot water using either the gas boiler or the electric immersion heater.
The original problem:
We previously had issues with our hot water, and a technician came out and worked on the system. Afterwards, we could heat the water using either electricity or gas.
However, the electric immersion heater has since stopped heating the water properly. Turning on the usual electrical switch no longer produces hot water.
More recently, another technician came out and said the gas boiler should be able to heat the cylinder. He noticed that the cylinder thermostat was set relatively low, so he increased it. He also showed me which pipe should carry hot water towards the cylinder.
Unfortunately, that hasn’t resolved the problem.
What I’ve observed while troubleshooting:
1. The gas boiler works and the radiators get extremely hot.
When I turn on the gas boiler and central heating, the radiators heat up normally. They’re practically piping hot, so the boiler is clearly producing heat.
However, the domestic hot water remains barely lukewarm, even after leaving the heating running.
2. The pipe leading towards the cylinder gets hot at the top but progressively cooler further down.
There’s a copper pipe connected to the motorised valve labelled “HOT”.
The pipe near the motorised valve gets very hot, but as it travels down towards the blue hot-water cylinder, it becomes progressively cooler. The lower section near the cylinder is only lukewarm.
I don’t know whether this is normal or whether it indicates that hot water isn’t circulating properly through the cylinder’s heating coil.
Another pipe enters the cylinder from the top, but that one doesn’t appear to be getting hot either.
3. The motorised valves have AUTO and MAN settings.
There are three white Myson Power Extra motorised valves.
Two were set to AUTO, while the valve labelled HOT was set to MAN.
I experimented with switching the HOT valve from MAN to AUTO and then back again, but it didn’t seem to make any difference.
I also noticed that the little grey levers on the valves move with practically no resistance.
The red/orange indicator light on the HOT valve is illuminated when the heating is running.
I’m wondering whether the valve might be faulty, stuck, or not opening properly.
4. The hot-water cylinder itself doesn’t seem to be heating.
Even after running the gas heating for a while, the blue cylinder doesn’t feel noticeably warmer, and the water coming from the taps remains barely lukewarm.
5. The timer appears to be permanently ON.
There’s an Optimum 24-hour mechanical timer underneath the gas boiler.
Its selector is set to “I”, which I understand means permanently ON, bypassing the programmed schedule.
I’m not certain whether this timer controls the boiler, hot water, or another part of the system.
6. The electric immersion heater also doesn’t work.
This is the part that confuses me most.
If the issue is a faulty motorised valve preventing the gas boiler from heating the cylinder, wouldn’t the electric immersion heater still work independently?
The immersion previously heated the water using a wall switch, without needing the gas central heating.
Now neither method seems to heat the water properly.
This makes me wonder whether there could be a shared issue with the cylinder, its controls, or the delivery of hot water to the taps, rather than simply a faulty motorised valve.
My questions:
Does the temperature difference along the pipe suggest a faulty motorised valve or poor circulation through the cylinder?
Is it normal for the Myson Power Extra manual levers to move with almost no resistance?
Could the cylinder thermostat or heating controls explain why the gas boiler isn’t heating the stored water?
What could explain both the gas heating and electric immersion failing to provide properly hot tap water?
Are there any simple, safe checks I can carry out before paying for another technician?
I’ve already had someone inspect the system, but unfortunately the problem persists.
I’ll attach photographs of the boiler, cylinder, motorised valves, thermostat and timer.
I’m not planning to interfere with any electrical wiring, gas components or plumbing valves myself. I’m mainly hoping to understand what might be happening and what I should ask the next technician to investigate.
Any advice would be greatly appreciated. Thanks!