r/askaplumberUK • • 12h ago

Water not turning off to our house

1 Upvotes

We have an 80’s build house and have been living here for 3 years no problems. Recently, our toilet went wrong and would no longer flush.
We had a plumber out to have a look at it. He told us that there was no way of isolating the toilet itself in order to fix it.
He checked various cupboards around our house, including up in the roof.
He found the tap to turn of the water in our house was completely seized up and said it will snap if he tried to turn it off. He then went out on the road to turn our water off from the mains.
When he did this, the water continues to stay on in our property. Today we have had it switched off at the mains all day, yet we have continued to have fully working water and have done 3 loads of washing despite it supposedly being “off”.
We have a hot water tank and tank in the roof, but can hear that that is still refilling despite being off outside.

We have contacted our water supplier who has come out and has no idea either.

Also to add, our water has always been incredibly cheap (£30 a month, for a large 3 bed property with 3 of us living here). We have never questioned the price as we were first time buyers when we moved in, however, have about 14 showers a week, alongside 4 baths, dishwasher on every day and 3 loads of washing on every other day.
When we spoke to my mum who lives round the corner she said her water bill is double what we are paying and she doesn’t use nearly as much water as us.
We have also noticed that over the past 24 hours our water meter readings haven’t changed at all, despite lots of water being used at our property.

Does anyone have any ideas? Could the water not switching off to our house and incredibly low bills bd connected somehow? Thank you


r/askaplumberUK • • 12h ago

Water not turning off to our house

Thumbnail reddit.com
1 Upvotes

r/askaplumberUK • • 14h ago

Broken basin

Post image
2 Upvotes

r/askaplumberUK • • 15h ago

This shower won’t run cold

Thumbnail gallery
1 Upvotes

Posting here as well in hopes someone can help me get a non scalding shower.


r/askaplumberUK • • 17h ago

Danfoss BEM 5000 random clicking bursts

1 Upvotes

Hey all, is this normal? Bought a house with a BEM 5000 and every now and then it will randomly burst clicks, over a few minutes then go silent for ages. The lights on the front don't seem to change. Never had one of these before so is this normal? Many thanks!

P.S. sorry for the camera angle, I was trying to listen to where the clicking was coming from!


r/askaplumberUK • • 20h ago

Can't get rid of air in system Worcester Greenstar Si Compact

1 Upvotes

I'm trying to understand what is happening and advice needed.

Boiler had it's annual service a couple of months ago. Also replaced a radiator to warm up the bathroom a bit better. There was air in the system before but now it seems a lot worse. Rads have been bled again and again and all look fine. There is no loss of water pressure in the boiler but I have topped it up to replace the water removed from bleeding. Water and CH is working fine apart from the gurgling from the pipes.

I run Air Purge for about 10 to 15 minutes and this sorts the problem for about half an hour but then the gurgling starts again.

I have checked all rads and cannot detect any leaking water.

I will be travelling abroad for three months in the next week so the whole system will be switched off. I am hoping this will be fine until I get back when I can get it fixed properly but I would like to know what is going on and what I need to do to fix it.


r/askaplumberUK • • 21h ago

A-01 Vokera boiler fault

0 Upvotes

We are having issues with our boiler, it is a Vokera by Riello boiler and keeps coming up A-01 fault code, we have tried to reset the boiler a good few times and it’s as if it’s firing up then goes red and the same code comes up again, I’ve had a look online and when we turn to run the hot tap and turn it back on it tried to fire up again but just getting the same code again.

We have had a few different engineers out who said everything looks good, electrodes fine, pressure fine and even the condensator, most likely to be the PCB.

Has anyone else had this issue and did this end up being their PCB needing replaced? Been told it’s a bit expensive to have replaced but it’s an absolute must!

I’m currently 6 months pregnant and needing this sorted ASAP!


r/askaplumberUK • • 1d ago

Valliant TimeSwitch 150 keeps getting stuck on- for example today I got home in the evening and when I checked the timer it had got stuck at 2pm(the end of an "on" period) and the heating had been on that whole time - I turn the dial to the correct time and it works for another few days then gets st

1 Upvotes

r/askaplumberUK • • 1d ago

Gas boiler heats radiators but not hot-water cylinder. Electric immersion also stopped working. Any ideas? (Ireland/UK-style system)

Thumbnail
gallery
1 Upvotes

Hi everyone,
I’m based in Dublin, Ireland, so just to clarify upfront, this is an Irish/UK-style domestic heating system, not an American setup.
I’ve been having ongoing problems with my hot water and would really appreciate some advice from anyone familiar with these systems. I’m not particularly knowledgeable about plumbing or heating, so apologies if I misuse any terminology.
My setup:
Gas boiler: Glow-worm Energy 18s.
Hot-water cylinder: Large blue insulated storage cylinder with an electric immersion heater.
Motorised valves: Three Myson Power Extra valves, one apparently labelled “HOT”, which I believe controls the hot-water circuit.
Cylinder thermostat: Orange thermostat attached to the side of the cylinder.
Timer: Optimum mechanical 24-hour timer, located underneath the gas boiler.
Room thermostat: IMIT dial thermostat.
As far as I understand, the system should allow us to heat our domestic hot water using either the gas boiler or the electric immersion heater.
The original problem:
We previously had issues with our hot water, and a technician came out and worked on the system. Afterwards, we could heat the water using either electricity or gas.
However, the electric immersion heater has since stopped heating the water properly. Turning on the usual electrical switch no longer produces hot water.
More recently, another technician came out and said the gas boiler should be able to heat the cylinder. He noticed that the cylinder thermostat was set relatively low, so he increased it. He also showed me which pipe should carry hot water towards the cylinder.
Unfortunately, that hasn’t resolved the problem.
What I’ve observed while troubleshooting:
1. The gas boiler works and the radiators get extremely hot.
When I turn on the gas boiler and central heating, the radiators heat up normally. They’re practically piping hot, so the boiler is clearly producing heat.
However, the domestic hot water remains barely lukewarm, even after leaving the heating running.
2. The pipe leading towards the cylinder gets hot at the top but progressively cooler further down.
There’s a copper pipe connected to the motorised valve labelled “HOT”.
The pipe near the motorised valve gets very hot, but as it travels down towards the blue hot-water cylinder, it becomes progressively cooler. The lower section near the cylinder is only lukewarm.
I don’t know whether this is normal or whether it indicates that hot water isn’t circulating properly through the cylinder’s heating coil.
Another pipe enters the cylinder from the top, but that one doesn’t appear to be getting hot either.
3. The motorised valves have AUTO and MAN settings.
There are three white Myson Power Extra motorised valves.
Two were set to AUTO, while the valve labelled HOT was set to MAN.
I experimented with switching the HOT valve from MAN to AUTO and then back again, but it didn’t seem to make any difference.
I also noticed that the little grey levers on the valves move with practically no resistance.
The red/orange indicator light on the HOT valve is illuminated when the heating is running.
I’m wondering whether the valve might be faulty, stuck, or not opening properly.
4. The hot-water cylinder itself doesn’t seem to be heating.
Even after running the gas heating for a while, the blue cylinder doesn’t feel noticeably warmer, and the water coming from the taps remains barely lukewarm.
5. The timer appears to be permanently ON.
There’s an Optimum 24-hour mechanical timer underneath the gas boiler.
Its selector is set to “I”, which I understand means permanently ON, bypassing the programmed schedule.
I’m not certain whether this timer controls the boiler, hot water, or another part of the system.
6. The electric immersion heater also doesn’t work.
This is the part that confuses me most.
If the issue is a faulty motorised valve preventing the gas boiler from heating the cylinder, wouldn’t the electric immersion heater still work independently?
The immersion previously heated the water using a wall switch, without needing the gas central heating.
Now neither method seems to heat the water properly.
This makes me wonder whether there could be a shared issue with the cylinder, its controls, or the delivery of hot water to the taps, rather than simply a faulty motorised valve.
My questions:
Does the temperature difference along the pipe suggest a faulty motorised valve or poor circulation through the cylinder?
Is it normal for the Myson Power Extra manual levers to move with almost no resistance?
Could the cylinder thermostat or heating controls explain why the gas boiler isn’t heating the stored water?
What could explain both the gas heating and electric immersion failing to provide properly hot tap water?
Are there any simple, safe checks I can carry out before paying for another technician?
I’ve already had someone inspect the system, but unfortunately the problem persists.
I’ll attach photographs of the boiler, cylinder, motorised valves, thermostat and timer.
I’m not planning to interfere with any electrical wiring, gas components or plumbing valves myself. I’m mainly hoping to understand what might be happening and what I should ask the next technician to investigate.
Any advice would be greatly appreciated. Thanks!


r/askaplumberUK • • 1d ago

ideal logic heat 18 (flow temp dial)

Post image
0 Upvotes

Howdy.

what temps does the dial represent?

Currently where it is and the 'e' symbol?

I've checked their manuals and they don't specify. Chatgpt reckons it is 55 degrees ish and 'e' is 60-65

If anyone knows for certain would be great to know.

Thanks


r/askaplumberUK • • 1d ago

Shower Hose with Hex Nut on both ends

Post image
2 Upvotes

I need to replace a shower hose but it has a hex nut on both ends. I'm struggling to find a replacement. I need it to be 1m long. All help is welcome


r/askaplumberUK • • 1d ago

Leaky radiator

1 Upvotes

My plug-in radiator drips a very small amount of liquid when it’s running. Anyone know what’s going on here?


r/askaplumberUK • • 1d ago

what steps should I take returning back to flat after 3 months being empty

Thumbnail reddit.com
1 Upvotes

r/askaplumberUK • • 1d ago

Had a boiler service recently, and since then mixer shower hot water only stays mildly hot…? Mixer shower is a few months old, used to get really hot before - what could be cause

Thumbnail reddit.com
1 Upvotes

r/askaplumberUK • • 1d ago

Geberit toilet duofix delta noise

1 Upvotes

Hi, from where it is coming this noise? I got out the valve, washed it but no difference. Should be this complety replaced?


r/askaplumberUK • • 2d ago

Loud rumbling and banging noise when my boiler ignites. Any ideas?

3 Upvotes

I have an Ideal Mexico HE18 boiler with a conventional central heating system.

I recently had a plumber round to install new thermostatic radiator valves (TRVs) and check the radiators. One radiator had sludge in it, which the plumber cleaned out.

Since then, I've noticed a loud rumbling and clanging noise around the pipe/flue area when the boiler (on floor) fires up after being off for a while. It happens exactly as the burner ignites and lasts a couple of seconds before stopping. Also the boiler displays a L9 which means the boiler has locked itself out to stay safe, and it has stopped heating until the fault is dealt with so I have to reset the boiler.

The plumber came back for a second visit and suggested it could be the heat exchanger or circulation pump.

Has anyone experienced anything similar, or know what might cause this noise?


r/askaplumberUK • • 2d ago

Is this an acceptable job?

Thumbnail
gallery
0 Upvotes

Paid a plumber to seal my tub, and was surprised by how it turned out. Would love an opinion from other professionals.

Edit: sorry should add that apparently there's a big gap between the tile and the tub so there was an existing piece of something, maybe plastic or silicone? between the tub and the tile, so the sealant was covering that. I was not home but apparently they said pulling it all out was a big job and this was easier/faster.

Also, plumber was in to replace the plug, which is why we had a plumber do this.


r/askaplumberUK • • 2d ago

Radiator cold

Thumbnail reddit.com
1 Upvotes

r/askaplumberUK • • 3d ago

Bath drain and overflow

Post image
2 Upvotes

Wanting to replace the bath plug and overflow but struggling to remove both parts, i have removed a grubscrew from the overflow but still not coming off and the drain there is no sign of a fixing screw beneath the plug, any help much appreciated


r/askaplumberUK • • 3d ago

Bubbles to test for leaks?

1 Upvotes

Is there a way to locate leaks or possible air getting drawn into my central heating? All the pipes etc are in the loft due to having a concrete floor etc and there a few automatic air vents up there etc. Could they be drawing air in?

I know plumbers use a spray to test for gas leaks (bubbles) is there an equivalent test/product i could use going around all the pipe joints, rad valves etc?

TIA


r/askaplumberUK • • 3d ago

Immersion Heater (& electric flat help)

Post image
1 Upvotes

r/askaplumberUK • • 3d ago

Water in pressure gauge

Post image
2 Upvotes

Baxi boiler, any ideas what the issue is here? Big job?


r/askaplumberUK • • 3d ago

What size cap should be used here?

Thumbnail gallery
1 Upvotes

r/askaplumberUK • • 3d ago

Given up on my hive control - want to go back to hard wired thermostat/reciever - how would I do this?

Thumbnail reddit.com
1 Upvotes