r/firealarms • • 1h ago

New Installation Notifier N16 silencable alarms

4 Upvotes

Hey all,

My company has started installing the N16 panels and I've ended up becoming the go to tech to program them. The issue I'm having is I cannot get the signal silence button to function on the touchscreen display. I've set all the detectors to be "yes/resound on fire" in the silenceable section in verifire tools.

I've also noticed a lot of settings are off or default to nothing unlike the NFS320 series for example.

Earth fault detection is off, NACs are off, silencable is set to no. Is that just how the panels are coming now? I know there's a new firmware available that allows you to turn on the NACs from the front facing display, but this seems like a silly setting to have off out of the box.


r/firealarms • • 6m ago

Discussion Advice on getting into the field

1 Upvotes

Hi all,

Thanks in advance for getting any replies. I'm working on a career change, and considering low voltage work, including fire alarm systems. I've been doing standard residential electrical (mostly new construction) for about 6 months. Brand new to the trades so kinda faking it til I make it, but I'm doing well. Low voltage work seems appealing because supposedly it's not as hard on the body as pulling service feeds in 100 degree heat.

I've applied to IBEW 98's telecom division apprenticeship but the test/interview process isn't until spring time, so I'm considering applying to some fire alarm companies beforehand to avoid putting all my eggs in one basket.

Curious if anybody has recommendations to get ready for job applications. I have my OSHA 10, but should I bang out the 30hr? I see that you can take the NICET 1 test before actually having the work experience. Do y'all think it's worth it to put in that effort on the front end, or should I just shoot my shot and try to get an employer to prep me for that? Any rec's for courses or other resources for learning?

Thanks again


r/firealarms • • 1d ago

Meme Another FACP in GTA 6!

Post image
341 Upvotes

r/firealarms • • 7h ago

Technical Support Simplex 4020 help

1 Upvotes

Posting a second time because I need a few more answers prior to going back to the site

This started on the beginning of the week. I was working on an old 4020. The panel had a trouble for short on the map net card 3, and a communication failure on the same card.

At this point, there was no voltage on the card and I couldn’t even flash the LED because it said it couldn’t communicate with the card.

The card question is a 565 – 368D so we ordered a used one off-line.

At first I installed the new card and every other card also went into communication failure. After messing around with it, be a little and restarting the panel I got to a point where I had the same two troubles as original, however, I was able to flash the LED now.

I also had a random moment where it seemed like it started communicating with devices because a random pull station went into alarm, however I couldn’t even reset that pull after removing it because it no longer seemed to be communicating with the panel. I even attempted to flip other pull stations it did nothing.

Essentially, I had to restart the panel again and get back down to those two troubles I started with.

Obviously, I did check to see if there was actually a short on the field wiring or if voltage would return if the field wiring was removed, but I did not.

A quick sidenote- I did speak to a buddy at JCI and he mentioned this so in case anyone else asks - apparently when he looked up that card, he was trying to tell me it is not the map net Card however like I mentioned, I am able to flash the LED on the map net card and there is no other card it could be.


r/firealarms • • 1d ago

Fail Artificial intelligence fire detection system mistakes image as actual fire

128 Upvotes

This is why we don’t trust AI.


r/firealarms • • 16h ago

Meme Weekly /r/FireAlarms Memes - Share your Memes!

0 Upvotes

r/firealarms • • 2d ago

Proud Enthusiast FACP!! GtaVI

Post image
201 Upvotes

I saw someone posted some pull stations and AVs well here the FACP.


r/firealarms • • 1d ago

Technical Support Simplex technicians HELP

2 Upvotes

This started on the beginning of the week. I was working on an old 4020. The panel had a trouble for short on the map net card 3, and a communication failure on the same card.

At this point, there was no voltage on the card and I couldn’t even flash the LED because it said it couldn’t communicate with the card.

The card question is a 565 – 368D so we ordered a used one off-line.

At first I installed the new card and every other card also went into communication failure. After messing around with it, be a little and restarting the panel I got to a point where I had the same two troubles as original, however, I was able to flash the LED now.

I also had a random moment where it seemed like it started communicating with devices because a random pull station went into alarm, however I couldn’t even reset that pull after removing it because it no longer seemed to be communicating with the panel. I even attempted to flip other pull stations it did nothing.

Essentially, I had to restart the panel again and get back down to those two troubles I started with.

Obviously, I did check to see if there was actually a short on the field wiring or if voltage would return if the field wiring was removed, but I did not.

A quick sidenote- I did speak to a buddy at JCI and he mentioned this so in case anyone else asks - apparently when he looked up that card, he was trying to tell me it is not the map net Card however like I mentioned, I am able to flash the LED on the map net card and there is no other card it could be.


r/firealarms • • 1d ago

Discussion How are businesses handling POTS lines for fire alarms and elevators as copper gets retired?

Thumbnail reddit.com
4 Upvotes

r/firealarms • • 1d ago

Technical Support FireLite ES-200X Communications Light

3 Upvotes

I had a tech call me about a FireLite ES-200x, newly installed system. Panel display showing "System all Normal", monitoring report is showing the daily E602 signals, but the panel has the communication light on, and the on-board piezo sounding, which cant be silenced. Anyone else run into this issue, and how did you fix. I called up FireLite, and they said it just needs a power cycle. Wanted ya'lls opinion. Thank you


r/firealarms • • 1d ago

Technical Support an old burglar alarm used as a fire alarm?

Thumbnail
gallery
15 Upvotes

this dictograph panel had a bunch of smoke detectors wired in series to a single zone.

no key for it because it was just… always on.

i dont know what all the terminals do, cant tell if there’s an external trigger that could be used with an iot/retrofit board so it can do something useful like call for help.

any techs with vintage schematics and manuals know where to locate this manual X286? I’d peg its install date to somewhere around 1976-1984.

i may just end up sticking a new PCB inside here and reusing it just for the cabinet and status light.


r/firealarms • • 1d ago

Technical Support ESL 1500 Charging Circuit

1 Upvotes

Older members of the Brain Trust, question. Does the charging circuit of an ESL 1500 panel shut itself off if the batteries are not good? Panel in question was shut off with new-ish batteries. Now those batteries were dead, and the charging circuit did not read any voltage. Replaced batteries, low battery trouble light went off, but when pulling leads from the batteries, still read no voltage coming from the panel. Safety feature, or bad panel?


r/firealarms • • 1d ago

Discussion Have systems become to complicated or poorly trained staff ?

3 Upvotes

I worked at an alarm company in the 90s from 16th year on this earth till end of college. We had everything from basic systems that just rang a bell to complicated systems that could be used zone to zone.

Now 35+ years later I’m not in the industry anymore but still notice what’s out there and a few times had input on equipment, reset a few false alarms no one could figure out how to reset, to evacuating our office I work at.

We in the last five at our office got a multi function system. It still does everything the old system did. But it has built in PA system, an app, multi evacuation options and the ability to control it via our phone system in the office.

However I found on a couple occasions we needed to address the building and evacuate and those in charge at the time did not know how to operate it other then the pull station. Once instead of activating the “severe weather take shelter” option we had “active shooter” alerts paging on two floors and nothing in the basement level or floors 3-5. Another time a building manager was calling floor to floor to tell people to leave the building as she didn’t know how to activate a non emergency announcement.

Have we gotten too complicated with some of these systems or is it lack of proper continuing training.

I was never trained on our system when it was installed but reading the training book and just following the prompts was able to figure it out.

I ended up getting trained by the provider after being clubs out of when they learned I had some experience and held classes for new people who would be responsible during emergency. When I did my first few classes with existing maintenance and security staff over half didn’t know where the control panel was and a few who did said they “think” there is something in utility closet off the lobby. Don’t get me started on who knew and didn’t know the codes and announcement options or even what to dial on the phone to set off an alert. The coolest thing I do like on our system is (and I am not sure if it’s an add on) is you can sign up for text alerts. The text alerts do not go off for the active shooter or fire. I assume so a bunch of text notifications are heard and people are not evacuating timely because they are reading a text. But everything else they do.


r/firealarms • • 1d ago

Technical Support Edwards/Kidde CMS input

0 Upvotes

Hello, I am putting in an Evolve panel (this is the first one of the company) with the VS/FX/VM panels I have not had issues making it communicate properly with the CMS. I have the evolve programmed to send restorations, but it is sending a fire alarm when it comes in and a fire alarm when it restores. Anyone ran into this issue? I've talked to the monitoring and tech support and didn't get around.


r/firealarms • • 2d ago

Vent Stress

12 Upvotes

I got hired recently to be a fire alarm technician with zero experience and it’s been great but the stress has been getting to me. A lot of the costumers are used to the old techs from before and the training was not that much. I feel so slow on the learning end of this. I act like it’s all chill even when I call other techs and for help and it turns out I answered my own question when I called and they just explained it in a more complex way, and try to make me feel like a dumbass. And how small businesses are struggling only because the pm won’t communicate.

I’ve had stress before but it’s getting to the point of making my stomach so upset I’ve thrown up. Not during the job but today I felt it on my last hour. What are other paths that previous techs took when they realized the job wasn’t for them? I don’t want to become a job hopper so I want to stay with this a little more for the experience but afterwards I want to settle on something without dealing with pm and people being rude because I’m testing out an alarm.


r/firealarms • • 1d ago

Discussion Weekly /r/FireAlarms Bragging - tell us about your new gears, troubleshooting technique, swag!

1 Upvotes

Time to brag! New gear? New crew? On vacation? Personnal troubleshooting techniques? Come'on makes us jealous of you!


r/firealarms • • 2d ago

Vent Corporate

35 Upvotes

I don’t know, but fire alarm work feels like it’s gotten a lot more difficult with all the corporate stuff added on. My company has always been corporate, but in recent years it’s become nonstop emails, safety messages, meetings, and other things that have nothing to do with the actual trade.
Most of the time, I just want to do the fire alarm work I signed up for. I shouldn’t have to read 50 emails a day or sit through meetings that don’t apply to my job. It’s all extra, unnecessary bullshit, and honestly, it’s frustrating, man.


r/firealarms • • 2d ago

Proud Enthusiast They put actual fire alarm systems in GTA 6

Thumbnail
gallery
120 Upvotes

The detail in this game is WILD. These aren't just fake fire alarms. The airport in GTA6 has a full-fledged System Sensor system, complete with different parts of the building having different alarms as if they were built/renovated at different times.

I don't play GTA6, but I've been reccomended some shorts on it (this one is from Aaron Rheins)


r/firealarms • • 2d ago

Technical Support Just checking: this is a firmware issue right? It'll require getting a Siemens licensed tech out here?

Post image
9 Upvotes

Panel is Siemens Cerberus

Edit: THIS ISSUE HAS BEEN RESOLVED! THANK YOU TO THOSE IN THE COMMENTS


r/firealarms • • 2d ago

Work In Progress Xtra base

Post image
7 Upvotes

Has anyone ever seen this? We have replaced that SIM but still showing this on the panel.


r/firealarms • • 2d ago

Work In Progress nicet lvl 1

0 Upvotes

in a month I have my NICET lvl 1 exam are there any tips or recs to achieve this chapter?


r/firealarms • • 2d ago

Discussion Weekly /r/FireAlarms Discussion - Codes, Standards & Norms

1 Upvotes

hello there, if you have a question regarding an article in a specific book, please add the reference in you question in this thread. Thanks you!


r/firealarms • • 3d ago

Technical Support Output trou6on a sounder base

Post image
3 Upvotes

I was sent out to replace smoke/co head and sounder base still get the same trouble


r/firealarms • • 4d ago

Discussion I hate how some companies, like Sound & Signal Inc., they keep fire alarm system passwords to themselves after installation without even informing the customer. These fire alarm system passwords belong to the customer, not the installation company. I intend to report this to the Fire Department.

73 Upvotes