Discussion CAN/ULC s536-19 questions Addressible Testing - exam test prep?

1 Upvotes

I am a new trainee tech and wanted clarification on the standard on these check list items below for addressible systems for an exam. How do you perform these tests on addressable systems below? If someone can break these down for me that would be great. Also how can we create open circuits in addressible systems when I've heard that if you unplug some panels loops you can get map faults. Or if you short the loop you can get issues also. How do you navigate these issues while still inspecting the system to the standard.

Also how do you physically perform circuit fault testing on an isolator? Do you use a jumper wire to short the terminals? Again, would this cause any glitches or issues with the system when doing this??

1. Each system abnormal condition specified in Table 3.1 tested for each data communication link at the control unit or transponder.
2. Tests for alarm and trouble received under a single ground fault condition conducted on each conductor of that data communication link independently.
3. Each conductor in a data communication link, Class A (DCLA) tested for the capability of providing an alarm signal on each side of a single open circuit fault condition.
4. Where data communication link(s) are installed without fault isolation, impose a wire-to-wire short circuit fault on each data communication link during a non-fire alarm condition and confirm receipt of trouble and alarm conditions from each adjacent data communication link (record results in 23.3, Circuit Fault Tolerance Test Sheet).
5. where fault isolators are installed in data communication links serving field devices, impose wire-to-wire short on the isolated side during non-fire alarm condition, confirm annunciation of the fault, and then operate a device on the source side, and confirm activation at the control unit or transponder (record results in 23.3, Circuit Fault Tolerance Test Sheet). Thanks


r/firealarms • • 10h ago

Discussion Let's Rate Monitoring Providers

3 Upvotes

Curious what the community thinks about the current crop of monitoring providers out there, favorite and least favorites. Specifically would like to hear about experiences with Emergency 24, CMS Monitoring, Rapid Response, and AvantGuard/Becklar. Or others that are worth recommending or avoiding. We're looking at new options and I want some real world technician opinions.


r/firealarms • • 10h ago

Technical Support CAN/ULC s536-19 questions Addressible Testing - exam test prep?

1 Upvotes

I am a new trainee tech and wanted clarification on the standard on these check list items below for addressible systems for an exam. How do you perform these tests on addressable systems below? If someone can break these down for me that would be great. Also how can we create open circuits in addressible systems when I've heard that if you unplug some panels loops you can get map faults. Or if you short the loop you can get issues also. How do you navigate these issues while still inspecting the system to the standard.

Also how do you physically perform circuit fault testing on an isolator? Do you use a jumper wire to short the terminals? Again, would this cause any glitches or issues with the system when doing this??

1. Each system abnormal condition specified in Table 3.1 tested for each data communication link at the control unit or transponder.
2. Tests for alarm and trouble received under a single ground fault condition conducted on each conductor of that data communication link independently.
3. Each conductor in a data communication link, Class A (DCLA) tested for the capability of providing an alarm signal on each side of a single open circuit fault condition.
4. Where data communication link(s) are installed without fault isolation, impose a wire-to-wire short circuit fault on each data communication link during a non-fire alarm condition and confirm receipt of trouble and alarm conditions from each adjacent data communication link (record results in 23.3, Circuit Fault Tolerance Test Sheet).
5. where fault isolators are installed in data communication links serving field devices, impose wire-to-wire short on the isolated side during non-fire alarm condition, confirm annunciation of the fault, and then operate a device on the source side, and confirm activation at the control unit or transponder (record results in 23.3, Circuit Fault Tolerance Test Sheet).

Thanks


r/firealarms • • 10h ago

Technical Support Fire lite Ms-2410b issues

Post image
0 Upvotes

Hello,

My fire lite ms-2410b panel has these weird glitches where the LEDs will flash or blink really quick and in random spots at random times. It’s not just becuase the panel has troubles it’s just not right.


r/firealarms • • 13h ago

Discussion I hate how some companies, like Sound & Signal Inc., they keep fire alarm system passwords to themselves after installation without even informing the customer. These fire alarm system passwords belong to the customer, not the installation company. I intend to report this to the Fire Department.

44 Upvotes

r/firealarms • • 14h ago

Discussion Inspection Report Software Question

6 Upvotes

Anyone have experience with CodeGreen ITM inspection software?

I recently started at a small company that's been using paper inspection reports. We're starting to pick up some larger clients who are accustomed to more detailed, comprehensive reports, so we're looking into software options.

My previous company used BuildingReports, which I was never a huge fan of. From what I've seen on CodeGreen's website, it looks like it could be a good fit for a small 2–3 person company.

I'm curious about other people's experiences with the software, particularly the initial setup and data entry process when building out a new site for its first inspection. I haven't been able to find any videos or examples showing what that process actually looks like. They just say you can import from PDF or points list.

I'd appreciate any feedback from people who have used it!


r/firealarms • • 14h ago

Discussion Is it hard to get in as a fire protection service technician?

7 Upvotes

Is it hard to get in with no experience? I had a interview last Friday and this week would be a potential second interview. All they mostly asked was if I had a good driving record,mechanically inclined and willing to work with lifting over 50 pounds.


r/firealarms • • 20h ago

Fail You get what you pay for I guess

Post image
41 Upvotes

My company was out bid by someone else to replace a Siemens panel at a hotel. Now that company won't answer their calls so we took a look at the troubles on the panel. This is the 'finished' install.


r/firealarms • • 20h ago

Technical Support Inspire Question

1 Upvotes

Does Notifier have a slim cabinet for the Inspire like the Gamewell-FCI version does? I am trying to replace a Silent Knight 5207 that is recessed.

I cannot find one on the data sheet so figured I would ask the brain trust.


r/firealarms • • 20h ago

Discussion Fire Suppression System service and monitoring switch

0 Upvotes

On the facilities director of a church in texas. We are switching service and monitoring companies for our fire suppression system. The new company is trying to charge me an outrageous amount for switching when all the actual equipment is already set up. What should it cost to create a new cellular pathway?


r/firealarms • • 21h ago

Work In Progress Laundromat system

5 Upvotes

We have an opportunity to design/install a fire alarm in a self service laundromat. However, we nor any of my close contacts in the industry have installed a system in a laundromat before. The basics are easy enough and we feel like heat detectors are the way to go for detection vs smokes. But does anyone have a specific insight as dryer equipment relays, or what might be needed for venting systems and dryer banks? In our area the system is not “required” so the customer wants cheap. We have told them that it has to meet what we consider minimum protection as it is a giant liability issue if the system doesn’t work due to not enough protection.


r/firealarms • • 22h ago

Customer Support Resident in high rise, not sure fire alarm is working properly

Post image
6 Upvotes

greetings! hoping someone in this sub can give me some reassurance/insight. please see the pic of our high-rise building's fire alarm control panel for reference.

EDIT: Updated photos of panel are in my comment below now. The original pic was from 2 wks ago, now I have pics from today. Also confirmed that the “Troubles” screen is the exact same today that it was over 2 weeks ago.

context:

a month ago, we had significant water damage in our building, getting into the walls and wiring of most of the floors in the building. a few days after that, our fire alarm started malfunctioning, triggering false alarms randomly throughout the building, not sounding on all floors, and the fire dept not able to turn it off.

our property mgmt's messaging around the issue is unreliable—they told 2 residents everything is fine, 1 resident that the system was damaged by the water, and another resident that they're still working on repairs. we haven't gotten an update in writing since the day after it went haywire. but someone was able to take a look at the control panel, and would love this community's thoughts on the state of our fire alarm system if there's anything to be gleaned from that.

it’s been pretty nerve wracking living in a high rise and not being confident in the fire alarm, so really appreciate any insight, thx so much


r/firealarms • • 1d ago

Discussion CARRER CHANGE

2 Upvotes

I recently started an inspection only apprenticeship and hate it. It’s nice somedays but most days it’s just super boring and doesn’t feel hands on enough. My last place was definitely a dead end but at least there was a lot of work to do and i had a scene of purpose. honestly like learning alarms and have been doing it since i was at my last residential construction jobs. I’ve had a couple days on service and it was way better than inspection. Unfortunately at my company i can’t get on the service side and we sub contract install. When should i leave my current place in 3 months I’ll get my Nicet level 1 and alarm license. If i wait another year which i really don’t want to i get my level 2. I want some options for install company’s to switch to, if install/service will get me more of a scene of purpose, if it’s worth waiting, and if i should expect a pay cut. (Im also fine with any other low voltage type work or even fiber. I’ve been told most install jobs i will do install for fire alarm and security. I honestly like a variety so that would be great.)


r/firealarms • • 1d ago

Technical Support Firelite ES-1000X with wireless Swift devices.

1 Upvotes

Does anyone know if using the wireless swift gateway limits the number of modules per loop on a Firelite ES-1000? I know the ES-50 & 200 are limited to 99 per loop and the SK6820 is 109 but I cannot find anything about the ES-1000. First time doing a wireless system with the 1000 so I'm making sure it can handle everything. Any help is appreciated.


r/firealarms • • 1d ago

Discussion Anyone taken NICET FAS Level 3 recently? Confused about IBC vs NFPA 101

7 Upvotes

If you’ve taken Level 3 since the March 2024 update, I’m curious how you handled questions where both the IBC and NFPA 101 might apply.

For example, if a question asked whether a building needs a fire alarm system, how would you know which book to use?

On the exam after the March 2024 update, did the questions name the code, or were there clue words like “Group B” or “existing”? Or was it something else entirely?

However it worked for you, I’d love to hear about it. Also curious if NFPA 101 even came up much on your exam.

Thanks!


r/firealarms • • 1d ago

Discussion Career changers

4 Upvotes

How can one get some idea if this would be a good fit, or if opportunities will be available long term?

I can learn the codes and I'm comfortable working with tools. I'm thinking a fire alarm inspector might be a reasonable fit.

50 yr old female, quick study, no tech background, but degree in technical communication; former teacher.


r/firealarms • • 2d ago

Discussion Advice: New Boss Wants me to start doing Fire Alarm and Sprinkler Inspections as a 1099

12 Upvotes

Hi. So tomorrow starts me second week with a small shop run by Mr. Z. He is a real master Electrician and has a business doing fire alarm /sprinkler system inspections, small repairs, etc in DC, MD, and VA.

So, after one more week with him (that would be 9 days total training), he wants me to go off independently to do these inspections. The thing is, he wants me to be a 1099 worker, an independent contractor. So, I have no license and as a 1099 I am not his employee. So legally, I am not authorized to sign inspection forms or tags.

I have to bring it up to him tomorrow. I guess all I can say is that I either need to be a W2 employee for his company to be under his license so I can sign off on inspections or that I can be a 1099 helper who doesn't sign off on inspections.

Does this sound crooked to anyone with experience? Any advice? Thx.


r/firealarms • • 2d ago

Discussion Was told this is okay—is it?

Thumbnail
gallery
12 Upvotes

I live in a 50 unit condo building. The hoa recently was told we need to update our fire alarm system. It was 25 years old. Most fire pulls are in common areas/hallways but on the 2nd floor, where people have their own egress to the street, each unit also has a fire pull.

The new fire pulls are larger than the old ones. I’m an owner and what I was told would be a quick change turned into a problem.

The old unit was mounted very close to a corner, and to the right of the old unit is a steel beam because it’s a French door system to the right. The new box doesn’t fit so they wanted to cut into my kitchen pantry door frame to mount it. I used ChatGPT to show what they wanted to do. I wanted a fire inspector or someone to assure me that mounting behind where a pantry door opens, into a door frame cutout is proper placement and allowed. They really pushed me to just accept this placement which seems shoddy. I asked if I could get a quote for relocating the fire pull to the opposite side of the glass French door where there is an entire blank wall and ample space—at my expense. I’ve gotten a lot of pushback from my building manager and the fire company but finally they agreed to at least give me a quote for moving it to the opposite side.

After researching, it seems mounting it behind a door that is often open (it’s a Kitchen pantry door so it’s open all the time) may not have been up to code anyway. And maybe the old position was grandfathered in, but if they are updating the system, can they keep it behind a door opening?

The other units don’t have this problem because all of them had their fire pull mounted on a different wall. It may have been a mistake when the building was built, who knows.

Can an expert weigh in? Is cutting into a door frame and installing it like that best practice?

The last photo is our kitchen in its natural state-my teenage neither was visiting and being funny so I took a photo but you can see the pantry door on the back is open—as it often is—and the fire pull would be mounted there.

Basically should I push to relocate to the opposite side of the French door where there is a blank wall and tons of space so the fire pull is accessible and mounted correctly?


r/firealarms • • 2d ago

Technical Support Notifier NFS2-3030 visuals do not come on.

Post image
5 Upvotes

Before I leave location. Is power supply bad, or is it something else?

Four circuits of visuals coming from one power supply(CPS-24) do not light up. When I go into the system, I got message that it has no answer. (all four circuits).

Thank you.


r/firealarms • • 3d ago

Discussion What's the difference between the "Alert" alarms and "Fire" alarms in commercial buildings?

1 Upvotes

Both are ceiling mounted units with the strobe light. The "Alert" ones are usually white with red text and the "Fire" alarms are usually red with white text, though I've been seeing more red on white lately. What's the difference?


r/firealarms • • 3d ago

Discussion Did anybody else know you could get the voice evacuation messages off of the AMG-1 from a ONYX2 series panel?

Thumbnail
youtube.com
0 Upvotes

Oh and I'm not talking about the first GEN 640

(the video is mine)


r/firealarms • • 3d ago

Discussion Whats need for own fire alarm business

2 Upvotes

Ok guys long winded question. I am currently 10yrs in as a fire alarm PM. 6 yrs install and remaining 4 as a PM. Have my nicet 2 working on getting my 3 and my CSA license.
Earlier this year I started a llc to contract myself as a sub for another small self owned fire alarm company. (1 guy who owns his own company). He contracts me to do the physical labor on projects he doesn’t have time for or doesnt want to do lol.

I started this as a side gig to get some extra cash and to dust off my install skills. In a perfect world if I could get paid the same I’d be installing instead of PM.

Ok time for the actual question. I am dancing with the idea of doing my own thing full time. I would like to know from the people who have started their own companies what is necessary for pulling permits, finding leads on bid projects, monitoring panels, setting up inspections? How did you guys go about getting all this stuff in order? All logistical stuff is what I’m still wanting to figure out.


r/firealarms • • 3d ago

Proud Enthusiast Simplex 2901-9838 Horn with a 4903 plate. Wondering what year this was installed hypothetically.

Thumbnail
gallery
6 Upvotes

when do you guys think this was installed? the hornstrobe is on the sand island center building in Hawaii. the pull station is the “dual action” t bar.