Discussion CAN/ULC s536-19 questions Addressible Testing - exam test prep?
I am a new trainee tech and wanted clarification on the standard on these check list items below for addressible systems for an exam. How do you perform these tests on addressable systems below? If someone can break these down for me that would be great. Also how can we create open circuits in addressible systems when I've heard that if you unplug some panels loops you can get map faults. Or if you short the loop you can get issues also. How do you navigate these issues while still inspecting the system to the standard.
Also how do you physically perform circuit fault testing on an isolator? Do you use a jumper wire to short the terminals? Again, would this cause any glitches or issues with the system when doing this??
1. Each system abnormal condition specified in Table 3.1 tested for each data communication link at the control unit or transponder.
2. Tests for alarm and trouble received under a single ground fault condition conducted on each conductor of that data communication link independently.
3. Each conductor in a data communication link, Class A (DCLA) tested for the capability of providing an alarm signal on each side of a single open circuit fault condition.
4. Where data communication link(s) are installed without fault isolation, impose a wire-to-wire short circuit fault on each data communication link during a non-fire alarm condition and confirm receipt of trouble and alarm conditions from each adjacent data communication link (record results in 23.3, Circuit Fault Tolerance Test Sheet).
5. where fault isolators are installed in data communication links serving field devices, impose wire-to-wire short on the isolated side during non-fire alarm condition, confirm annunciation of the fault, and then operate a device on the source side, and confirm activation at the control unit or transponder (record results in 23.3, Circuit Fault Tolerance Test Sheet). Thanks