r/hvacadvice • • 1h ago

Navien boiler - help programming night heating.

Post image
1 Upvotes

Hi there, does anybody know how to set this boiler to automatically keep warm during the night, without me having to wake up and turn it off?

I tried fumbling with the controler, read the manual, but it seems it has 6 programs, and it's not clear to me how that works.

Say I want to heat my home from 10pm to 7am automatically.

Programs have a starting time, but no stopping time.

If I ser one program for 10pm, will it start heating before, or exactly at 10pm?

Then, I suppose it'll stop once that temperature is reached, right?

Would programming 4 times, 2 hours apart fix it? Say, 2am, 4am, 6am, 12am, 10pm.

Would tha suffice?

Thanks you!


r/hvacadvice • • 2h ago

No heat Temporary fan fix while waiting for board? Freezing weather

1 Upvotes

Hi - I’m in an urgent heat situation and would appreciate some insight. The blower fan on my Trane XR90 gas/ac setup stopped working after an old fan power wire came loose from the capacitor and scorched the side of the fan case, taking the relay(?) out in the process. We’ve since replaced the aged motor and capacitor (both tested and working) and a new 50A65-5165 White-Rodgers board will be here late next week (the current board is a White-Rodgers 50A65-475-04). Everything is working normally except for the fan. Temps are freezing here and the house is uncomfortably cold. Is there anything we can safely DIY to get the fan going temporarily so the furnace can heat? Can’t afford to bring in a specialist unfortunately, so giving this a shot. Thanks!


r/hvacadvice • • 3h ago

Filter advice

Post image
0 Upvotes

So I just wanted to make sure because AI is telling me there is no filter here.

The diagram shows “filter cover” where this silver tape is, but AI is saying because I have a grille in my ceiling, where I have changed filters before, that is where my hvac filters need to be changed (there is a grille in my ceiling that can be opened to replace filters with, it’s like 20x20x1 sizes)

This is a new house I’ve moved into and am learning about the hvac system. Am going to email my builders in the meantime but wanted to see what you guys thought


r/hvacadvice • • 4h ago

Ice on Bryant heat pump

Post image
0 Upvotes

It was about 30 degrees this morning. But I did not expect this. What's the cause?


r/hvacadvice • • 4h ago

Need advice on improving AC airflow to an extension room

Post image
1 Upvotes

I could really use some advice regarding my room's cooling and airflow issues.

Some context about my setup:

  1. I live in the Philippines, where humidity is typically high.

  2. My room has no windows and very limited ventilation.

  3. I use a Condura dehumidifier to help control humidity.

  4. The blue rectangular box in the attached floor plan indicates the location of my current AC unit (LG 1.5 HP).

  5. I have an extension area connected to my main bedroom where I keep my PC setup.

The problem:

The extension area doesn't receive enough cool air from my AC unit. There's a noticeable temperature difference between the main bedroom and the extension, especially when I leave the door open.

First attempt – AC only

I set my AC to 25°C and leave the door to the extension area open.

  • Main bedroom temperature: around 25–26°C

  • Extension room temperature: around 29–30°C

  • Dehumidifier: turned off

I also noticed that the power consumption reported by the LG ThinQ app increases significantly, reaching around 0.7–0.8 kW.

For comparison, when I close the door to the extension, the AC's power consumption typically ranges from 0.07 kW at its lowest to around 0.3–0.4 kW at its highest.

Second attempt – Using an air circulator

I purchased a Vornado 633BK air circulator and placed it underneath the AC unit, directing airflow toward the extension area.

With this setup:

  • Extension room temperature improved to around 28°C.

  • AC power consumption became more stable at approximately 0.45 kW.

Although the air circulator helped, the extension is still noticeably warmer than the main bedroom.

My current dilemma: Should I upgrade my AC?

I'm considering replacing my current LG 1.5 HP unit with a Daikin King 2 HP.

My current LG AC also has some issues. Whenever I set the temperature below 25°C, ice starts building up on the indoor unit.

I've already paid a technician ₱6,000 (approximately $100) to fix the issue, but unfortunately, the problem returned after just three days. I can no longer get in touch with the technician, and I don't want to keep spending money repairing an old unit that may continue giving me problems.

However, I'm not sure whether upgrading to a 2 HP unit would actually solve my cooling problem or if the real issue is poor airflow and air distribution between the two areas.

I'd appreciate your thoughts on the following:

  1. Would upgrading from 1.5 HP to 2 HP significantly improve cooling in both areas?

  2. Is my current problem more likely related to insufficient AC capacity or poor airflow and air distribution?

  3. Would a 2 HP unit be able to cool the extension area effectively, assuming I keep the door open?

  4. Are there better ways to distribute cool air between the main bedroom and the extension?

  5. Would you recommend upgrading to the Daikin King 2 HP, or should I consider another solution first?

I'm open to suggestions and would appreciate any advice from people with experience dealing with similar room layouts.

Feel free to ask if you need additional information about my room dimensions, AC specifications, or layout.

Thanks in advance!


r/hvacadvice • • 5h ago

Water Heater Water heater/AC/Heating question

Thumbnail
gallery
0 Upvotes

My apartment's water heater was repaired after some leaking pipes caused some water damage, but the lever valves used to control heating/air conditioning were terminated, and new pipes were installed directly into the top of the water heater. (Vertical - Heat / Horizontal - Cooling)

Based on the layout of these pipes, should the heating/cooling be automated based on what my thermostat is on, or could this have been overlooked during the repair?

The thermostat itself only has Heat - Off - Cool and doesn't seem to be a smart device by any means.

Thank you!


r/hvacadvice • • 5h ago

AprilAire humidifier melted the electrode

Post image
1 Upvotes

It shut off after it melted through the wire. The manual says to replace the wires every 3 years so check yours if it has been longer than that.

Edit, turns out there was a recall in 2023 that neither the installer nor the manufacturer notified me about. D-shaped connectors have the straight sleeve, O-shaped have a waist.

https://www.cpsc.gov/Recalls/2023/Research-Products-Recalls-Steam-Humidifiers-Due-to-Fire-Hazard


r/hvacadvice • • 5h ago

Weil McLain CGi series 3 boiler is refusing to reach temps above 140F. Replaced the control module twice. What next???

Thumbnail
gallery
3 Upvotes

On the coldest days, this series 3 cast iron boiler will fire, have a beautiful flame, and reach 140F, and stay there and run for almost 24 hrs. Never fluctuating temps ±1 degree. My utility bills are nuts.

My house is about 2600sq feet with 17 average sized rads.

I’ve read a few threads about this models original control module being an issue that contributes to limiting temps to 140, and last December I replaced it with one from SupplyHouse.com. It ended up not correcting the situation, but it got me through another winter.

This season, I decided to order another since I double-checked a few model number details and convinced myself I ended up with a CM for another series or something. New one arrives and it’s exactly the same from last December. Still, the new one isn’t firing to a temperature past 140.

So far I’ve
-dialed the “economy adjust” to “min”
-checked the heat sensor
-double checked aquastat
-new expansion tank(old one leaked)
-new inducer motor(probably not related)
-added new circulation pumps(hopefully not related)

I’m an electrician by trade, but am fairly versed in the functions of this model, and really don’t want to rely on a technician for this. There has to be something else I’m missing, and I’d love some advice.

Thanks in advance


r/hvacadvice • • 6h ago

General Combustion motor is no longer constantly running after replacing R1 relay.

Thumbnail
gallery
3 Upvotes

I replaced my combustion motor last week because it was failing. I found a new motor for $170 and installed it myself.

Then I noticed that the combustion motor kept running after the furnace shut off.

I reached out on here a few days ago and you folks suggested that it was a bad relay. I replaced the R1 relay and now the combustion motor shuts off normally. It no longer keeps running after the furnace stops.

My friend who is an electrical engineer came over, read the schematic, used his volt meter and helped me connect the wires properly. The relay was $14.

I also bought an ignition module just to have on hand in case mine fails.

Thanks for all of your help on this sub!!


r/hvacadvice • • 6h ago

Quotes Pricing on installing a dehumidifier

1 Upvotes

So I have a house that gets pretty humid. I am looking at adding a whole house dehumidifier. I had a local guy who comes very highly recommended. I will buy the unit e080. He would just be doing the labor. This is what he messaged me

First I sized the dehumidifier which should be the E080 according to their specs this should work perfect. I can’t buy it any cheaper than you can online so you can go ahead and order it. The labor and materials to install the dehumidifier in an emergency drain pan with a safety switch , the ductwork for the supply and return air piping, duct seal will be installed on all pipe joints to insure there is no air leakage, then all duct piping will be insulated. condensate piping from the dehumidifier and the emergency drain pan will be connected to a properdrain line for disposal

The unit will be turned on and checked for proper operation at completions x . Total cost labor and materials is. $2,200.00

Does this sound accurate? I was thinking more of the 1000-1500. I was originally going to try it myself and did some research but thought I would have someone come and take a look. I believe in paying people for their work I just want to make sure I am not overpaying.


r/hvacadvice • • 6h ago

Furnace Is this Soot?

Thumbnail
gallery
0 Upvotes

Looking over my furnace (Trane XL 80) and noticed a large pile of soot on the furnace surface. it appears to be falling out of what I think is the exhaust pipe. when I tap the pipe I can hear stuff trickling down into the furnace itself.

The red light is blinking normally, steadily and about once a second when the heat is on.

I already figured I need to call an HVAC guy but any idea why I have so much soot?


r/hvacadvice • • 6h ago

2015 Trane XL15i with failing compressor, what else should be replaced?

1 Upvotes

My Trane XL15i heat pump that was installed new in 2015 has been diagnosed as having a failing compressor. Luckily, I may be able to get a warranty replacement part for no cost but will have to pay for the installation (labor, r410a, etc for about $1000-$1500). While I wait for a bid for the warranty work, I wonder what other work should be done on this unit "while we are at it" so hopefully I will get at least another 10 years out of the unit (Or, are there enough other parts that may fail after the compressor that it isn't worth keeping? A new unit is about $10k and I am trying to save money.)

I already replaced the two start capacitors since they were failing. The contactor is likely original and is still working at least for now. The big fan motor at the top of the unit is still running. Should I just go for the compressor and wait for the next shoe to drop?

Or, as I type this, I wonder if you all will say "junk it! it will be a money pit!" :-)


r/hvacadvice • • 7h ago

General necessary headroom for a mini split ac unit and crown molding.

1 Upvotes

Bought a mini split ac unit with intention of putting large garage shelving below it, said shelves will leave me with around 3 inches below the unit if i put it up against the crown molding which has a head room of roughly 3inches,

a tech who i had come out to quote the job mentioned that it would need a little room to get the cover off for maintenance and was open to the idea of me cutting the crown molding (i hate it anyways) where it would sit so i’d have the full 3 inches rather than having to deal with the angle of the crown molding.

my primary question is which direction should i take inches from, about 6 inches of play room so I’m not sure what my best bet is, i’m decently set in my plans as the space i’m working with is very limited.


r/hvacadvice • • 7h ago

Replaced Thermostat and now AC is short-cycling!

2 Upvotes

so my family and I had an old thermostat and the LCD display on it broke, we ordered a smart one, but that didnt work out due to put of date wiring that wasn't compatible with the new tech. we got a cheap new thermostat from walmart and had two extra wires that google told us to cap and leave alone (white and tan). we plugged in the wire, cut and stripped them too, but now after everything we try it keeps short-cycling (or at least that was the internet calls it. idk about all this stuff. its like turning off and restarting it it works for about a min before shutting off) We’re in fl and its soo hot and moneys tight so it might be a but before we can call a tech! please give us troubleshooting ideas!!


r/hvacadvice • • 7h ago

Thermostat Family member needs a new thermostat and i never worked with carrier

Post image
3 Upvotes

Hi , a family member reached out to me (I'm an apprentice HVAC tech) because their carrier infinity thermostat is starting to show it's age. The room temp isn't working properly (he has to go in a menu and then back to home screen for it to show the real current room temp) and sometimes the up and down buttons in the menu aren't working. A company has quoted them around 1500$-1600$ to come change the thermostat...

I know that changing it to a regular non communicating 24V would remove the modulating fan control and bring it to a 2 stage mode but other than that do you have any advices?

I mostly work with midea, Emerson, ecobee, techmore or Google nests thermostats

Thanks in advance!

PS. I don't have a picture of their furnace at the moment but they have an electric furnace paired with an a/c unit


r/hvacadvice • • 8h ago

No heat Help! Intermittent outages on goodman gas heat

1 Upvotes

I’ve been dealing with this since last winter. Multiple companies. None can figure out what is wrong. Sometimes it works, sometimes it does this. The flame sensor has been changed. Everything cleaned. Any ideas? I’m desperate for help.


r/hvacadvice • • 8h ago

Boiler Radiators

1 Upvotes

My girlfriend and I bought a house in the spring and only about 1/3 of the radiators work and in the ones that do work only a few of the coils actually get hot. They all have relatively new legend air T-60A adjustable air vents that don’t seem to be doing anything. The control valves are all the way open. The boiler seems to be working fine. I’m a pretty handy guy but most of the advice I can find tells me to bleed the system but that should happen automatically with the adjustable air vents open. Any advice is appreciated thanks


r/hvacadvice • • 8h ago Bravo

Quoted $2000 per A/C for cleaning

6 Upvotes

Own a large house w/ 3 A/C units. Have an HVAC maintenance plan where the tech checks it twice a year. Every technician has said "you have dirty coils in the blower and on the condensor." Okay. $2000 to clean each of the three outside condensors and another $2k to clean the inside coils. Claimed they needed to be, essentially, stripped and acid cleaned. Inside units same thing except they would have to drain the freon, cut the copper, clean them, replace, purge, and re-add the freon. So, if they were going to do it, it would cost >$8,000.

I finally got around to cleaning them today. Used a paint brush to wipe away the dirt inside the blowers. I thought there was more but no; I literally brushed off they stuff they showed me on the camera.

Outside, took off the covers, used a nylon brush to gently pull off the matted fibers (our dryer vent is about 5 feet away from where the condensers are). Then used a cleaner to wash them.

Long story short, accomplished the cleaning in about four hours and $40 in supplies. It took so long because the outside units are about two feet from the porch and you have little room to work.

EDIT: Yes, I cleaned the blower units inside the house. Only one of them actually needed it and that was a couple of sweeps w/ the paintbrush, not like they made it sound.

The outside units were worse but mostly because the previous owners did effectively no maintenance on the house before we moved in. Brushed/vacuumed off the lint then used a condenser cleaner and rinsed it off.

Also, tech said the box plenum the "dirty" blower was on was leaking which caused the build up. Uh huh. That plenum was part of the original build. There was not 9+ years of debris in the blower.

Going to cancel our maintenance contract on Monday.


r/hvacadvice • • 9h ago

No cooling Lennox cooling system add on to Braemar not cooling

1 Upvotes

Does anyone have a Lennox cooling system add-on to their Braemar ducted heating? Ours has been an absolute nightmare. Ever since the 7-year warranty expired, it seems to break down every single year. The technicians come out, fix it, and without fail, the same issue happens again the following summer, right in the middle of peak heat.

It’s been an absolute shit show. Has anyone else experienced this? It's becoming too costly now.


r/hvacadvice • • 9h ago

HVAC Contractors? (Not Company)

0 Upvotes

I'm looking for an installer labor only. This would include ductwork adn unit. Doe anyoe have a recommendation near Denton? Thanks!


r/hvacadvice • • 9h ago

Furnace Repair or replace 1972 Rheem 3204-50HD

Thumbnail
gallery
1 Upvotes

Central gas heater fires up but does not blow air. I want to repair this due to economic reasons but don't know how and HVAC technicians won't call back until next week. What do you think?


r/hvacadvice • • 9h ago

Worried I may have a minor carbon monoxide leak from dryer vent

Thumbnail
gallery
0 Upvotes

Hey so I recently noticed my gas dryer vent has a lot of dust and lint build up around the fittings I have a Carbon monoxide detector in the room but it never went off. is my landlord responsible for getting this fixed? any advice would be most appreciated


r/hvacadvice • • 10h ago

Boiler Would you rather ... Crawlspace installations

2 Upvotes

We are in the process of buying a house with a crawlspace and a pretty horrible existing furnace (duct work is holey and heat exchanger is cracked, plus oil tank is overdue for replacement). The crawlspace is gross ... So I think my options are:

  1. get a new furnace (horizontal, likely propane but could do oil again)

  2. switch to radiators and a boiler. Direct vent could be NOT in the crawlspace, we would add a little utility room.

I have Runtal radiators in part of my house today and I would probably want to use them in the new house, too. I love that they don't collect so much dog hair and dust as the normal fin-type ones.

It looks like it will be a lot to make the change. Radiators alone will be over $13k. Plus the boiler, and probably a bigger propane tank.

But it would get all the equipment out of the crawlspace, which seems better for maintenance and longevity. Any insight on what would be the better path? Goals are : Last home I will own, want to hopefully add mini splits later on for some cooling, and may add a second floor in the future. Limited funds, though.

If it was possible to someday tie in a heat pump to the system that would be awesome, but I don't know of that's possible. I WILL be hiring pros, I just want to have an idea of what I should be asking for.


r/hvacadvice • • 10h ago

Furnace What  pipe insulation would a pro use on this heat/hot water system?

Thumbnail
gallery
1 Upvotes

What  pipe insulation would a pro use on this heat/hot water system? Specifically, can I/should I use rubber foam pipe insulation on copper pipe runs going out of this hot water heating system, or do I need to use the fiberglass stuff… or something else?  It’s not a steam system but the pipes get quite hot (at least 140°F). 

Details: 

Previous owners of the house installed this system (see pics) in the last year or two. It delivers hot water to under floor radiant heaters in the main section of the house, to a few baseboard radiators in some rooms, and to the hot water tank, which is the potable hot water system. Howver, none of the hot water pipes in the system have any insulation, and the warmest room in the house is the uninsulated basement space with the heating equipment. I’d like to improve efficiency by insulating the pipes, but not sure if the regular foam stuff from the local DIY store is appropriate, as these pipes get pretty hot. (Not exact, but FWIW I put my Thermapen (kitchen thermometer) on the copper pipe coming out of the main boiler and got ~140°F.)