Hi I am changing a panelview 1000 to PV7 connected to a SLC05/4 . I am using a ANC-100e to connect them.
The migration from panelbuilder went ok , and some data are showed , and numeric input are working fine.
The problem I have is with the data from registers in N and F up then certain values .
With a N7:19 I can see the value, but with a N7:160. A message "Data Table N7:19 - N7:160 is too small or missing" ( N7 in Logix is 256 elements size ) , same as Float F31:11 is working great but with F31:72 fails , giving to me the same message , only changing to F Memory. (F31 is 255 elements size )
It seems to me , the HMI is asking more words than the DH+ can handle , but I am not sure if I am ok.
My question is , do I have to re map all the upper memory spaces to a new data table in lower memory spaces (for example N7:160 to N40:0) but is a lot of work , or there is another easier way to fix this .
I already try to put in a new screen one numeric indicator pointing to N7:160 , and it gives to me the same error message , just from 0 - 160 , am I missing something ?